Sauna electricity use

About a dollar in July, about two in January.

A sauna heater only draws power while it's on, and at full power a 6 kW heater uses 6 kWh an hour. A session is the heat-up plus however long you stay. Both stretch out in cold weather, so an outdoor sauna's running cost follows the thermometer.

6′ × 6′ barrel, 6 kW, one hour of use

5.9 → 11.8 kWh

About 5.9 kWh on a 68°F day and 11.8 kWh at 0°F. At MG&E's 18.4¢ per kWh, that's $1.09 to $2.17 a session. The U.S. average rate, 18.3¢, works out almost the same.

Estimate · EIA July 2026 rates

By outdoor temperature

kWh and cost per session.

A 6′ × 6′ barrel with a 6 kW heater and a glass door, heated to 176°F and used for an hour. MG&E is Madison's utility. California has the highest average rate in the lower 48.

OutdoorskWh per sessionMG&E · 18.4¢California avg · 33.6¢
80°F5.1$0.94$1.71
68°F5.9$1.09$1.98
50°F7.2$1.32$2.42
32°F8.6$1.58$2.89
20°F9.7$1.78$3.26
10°F10.7$1.97$3.60
0°F11.8$2.17$3.97
−10°F13.1$2.41$4.40
−20°F14.6$2.69$4.91

Physics estimate, ±20%. Every state's rate is in the calculator below.

Where the kWh go

Heat-up, then holding.

Heat-up. The heater runs flat out until the thermometer reaches temperature. On a 68°F day that's about 27 minutes for this barrel, or 2.7 kWh. At 0°F it's about 72 minutes, or 7.2 kWh.

Holding. Once it's hot, the controller cycles the heater just enough to replace what leaks out through the walls, glass and vents. On a mild day that's around half the heater's output. In deep cold it can be most of it.

Staying longer costs less than starting. A second hour adds only the holding power, about 3 kWh on a mild day. Two sessions back to back cost less than two separate evenings.

Compared with a hot tub. A hot tub is kept hot around the clock. A sauna uses nothing between sessions. Our cost guide compares a year of each at MG&E rates, and infrared cabins use less again, at the cost of the steam.

Calculator

Your rate, your weather.

Choose MG&E or any state's average rate, then set how often you'd use it and for how long.

Shape
6 ft
6 ft
Inside the hot room only. Leave out a porch or changing room.
Walls
10 sq ft
A full glass door is about 10–13 sq ft. A panoramic back window adds about as much again.
10°F
For an indoor sauna, use the room's temperature.
176°F
2
1 hour
Heater size
6 kW
Interior volume170 cu ft
Sizing volume, after walls and glass286 cu ft

Rated for this room: Harvia KIP-60 (170–300) · HUUM Drop 6 (177–353)

Circuit for a 6 kW heater
Draw25.0 A at 240 V

From the manuals: Harvia KIP-60: 10 AWG · HUUM Drop 6: 30 A breaker, 10 AWG. Your electrician sets the final breaker and wire to code.

Heat-up and running cost
50–75 min
Electricity per session10.7 kWh
Cost per session at 18.4¢/kWh$1.97
Per month$17

Physics estimate, shown as ±20%. It hasn't been checked against measured heat-up times yet. Send yours and help fix that.

Questions

Sauna power use.

How much electricity does a sauna use?

At full power, a heater uses its rating every hour: 6 kWh an hour for a 6 kW heater. A whole session, heat-up plus an hour of use, comes to about 6 kWh on a mild day and 12–15 kWh in sub-zero weather for a 6-foot outdoor barrel.

How much does it cost to run a sauna per session?

At MG&E's 18.4¢ per kWh, about $1.10 a session on a 68°F day and about $2.20 at 0°F for a 6-foot barrel with a 6 kW heater. Multiply the kWh by your own rate to compare.

How much does a sauna add to the electric bill each month?

Twice a week, roughly $9–10 a month in summer and $15–20 in a Wisconsin January at MG&E rates, for a 6-foot barrel with a 6 kW heater.

Does a sauna use power when it's off?

No, apart from a Wi-Fi controller on standby. The heater draws nothing between sessions. That's the big difference from a hot tub, which is heated around the clock.

Own a sauna?

Send us your heat-up time

Note the outdoor temperature and how long the thermometer took. We'll publish the reports together.

No name or email needed. We publish the reports in aggregate.

Sources and assumptions
  1. Harvia KIP heaters, 240V single-phase: rated room volumes, amps and supply wire (KIP-30, -45, -60, -80). Harvia KIP-60, Harvia KIP-80
  2. HUUM Drop heaters, 240V: rated room volumes, amps, breaker and wire (Drop 4.5, 6, 7.5, 9), from published spec sheets. Spec sheet
  3. Sizing adjustments: HUUM's method multiplies the volume by 1.5 for walls without at least R-13 insulation and adds 3.2 cu ft per sq ft of glass (4.8 if the walls are insulated). Harvia's equivalent: 1.2 m³ per m² of glass or uninsulated surface, and a factor of 1.5 for uninsulated log walls. HUUM sizing, Harvia support
  4. Electricity rates: U.S. Energy Information Administration, Electric Power Monthly Table 5.6.A, residential average by state, July 2026 (preliminary). MG&E residential rate as in our cost guide. EIA
  5. Heat-up model assumptions (handbook values): 42 mm solid wood walls with conductivity 0.11 W/m·K; framed walls at about R-13; single tempered glass at 5.8 W/m²·K; 6 air changes an hour through the vents; about 3.5 kg of stones per kW of heater; a 10 mm layer of wood (450 kg/m³, 1.7 kJ/kg·K) warming across walls and benches, starting at the outdoor temperature. Shown as ±20%. Not yet checked against measured heat-up times.